10--9

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

10.3.2 Manual Start

1.

Perform the Initial Setup procedures.

2.

On SSBM, turn the

SYSTEM MODE key switch to BYPASS momentarily.

If a bypass source is available when you turn the

SYSTEM MODE key switch to

BYPASS, the critical load is immediately supplied by the bypass source in Bypass

mode until the UPMs are available and the SSBM has been manually transferred to

Normal mode. The status indicators on the SSBM monitor screen indicate when the

Parallel Capacity/Redundant system is in Bypass mode and Normal mode.

3.

Observe that CBP and FBP have closed.

4.

On first UPM, set

BATTERY switch to ENABLE.

5.

On first UPM, turn the

MODE key switch to NORMAL for three seconds.

6.

Confirm the UPS breaker CB1 has closed by verifying breaker position on LCD

mimic screen.

The rectifier and input/rectifier cooling fans blowers should be running.

7.

Confirm UPS Battery Breaker CB2 (MBB) has closed by viewing breaker

position on LCD Mimic screen.
NOTE: If CB2 is a manual battery breaker, manually close CB2 after UPM

Battery Disconnected alarm and notification is received.

The inverter and output/inverter cooling blowers turn on. When the inverter reaches

full voltage, UPS breaker CB3 closes. It takes less than 1 minute for the UPS to

achieve Normal mode. If UPS is not in Autorestart, turn the

MODE key switch to

NORMAL for three seconds to transfer to Normal mode.

8.

UPS is now operating in Normal mode.

9.

Start remaining UPMs by repeating steps 4 through 8.

10.

On SSBM monitor screen, check for On Bypass, UPMs Ready message.

11.

If message appears, turn the SSBM

SYSTEM MODE key switch to NORMAL

momentarily.

12.

Observe that breaker CBS closes, breaker CBP opens, and the SSW is turned

off.