Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

Table O. UPM Output-to-SSBM Cable and Conduit Configurations: Based on UPM Manuals

UPM Output-to-SSBM Cable Configuration

Minimum Conductor Size, 3, (1) Neutral, (1) Gnd

Max No. of UPMs Connectable to each SSBM

(Based on UPM-to-SSBM Cable Configuration

9315

Model - kVA/kW

Output

Voltage

Output

Current

Conductor Size

(AWG or kcmil)

Number of

Conductors per

and Neutral

Number and

Size of Conduit

(in inches)

Model 2500

Model 3000

Model 4000

200 --- 200/160

400

290

4/0

2

2 --- 2.0

7

7

7

225 --- 225/180

208

625

350

3

3 --- 2.0

4

4

4

225 --- 225/180

480

271

3/0

2

1 --- 2.0

7

7

7

300 --- 225/180

480

271

3/0

2

1 --- 2.0

7

7

7

300 --- 225/180

600

217

350

1

1 --- 2.0

8

8

8

300 --- 300/240

208

830

500*

3

3 --- 3.0

4

4

4

300--- 300/240

480

360

250

2

2 --- 2.0

7

7

7

300--- 300/240

600

289

4/0

2

2 --- 2.0

7

7

7

250 --- 200/160

400

290

4/0

2

2 --- 2.0

7

7

7

250 --- 250/200

400

360

250

2

2 --- 2.0

7

7

7

400 --- 300/240

400

433

3/0

3

3 --- 2.5

4

4

4

400 --- 400/320

400

577

250

3

3 --- 2.5

4

4

4

500 --- 400/320

208

1110

600*

5

5 --- 3.0

2

2

2

500 --- 400/320

480

480

250

3

3 --- 3.0

4

4

4

500 --- 500/400

480

601

350

3

3 --- 3.0

4

4

4

500 --- 500/400

600

601

350

3

3 --- 3.0

4

4

4

625 --- 500/400

400

722

300

4

3 --- 3.0

3

3

3

625 --- 500/450

400

722

300

4

3 --- 3.0

3

3

3

625 --- 625/500

400

902

500

4

3 --- 3.5

3

3

3

625 --- 626/562

400

902

500

4

3 --- 3.5

3

3

3

750 --- 625/500

480

752

500

3

3 --- 3.0

4

4

4

750 --- 625/500

600

601

350

3

3 --- 3.0

4

4

4

750 --- 625/562

480

752

500

3

3 --- 3.0

4

4

4

750 --- 625/562

600

601

350

3

3 --- 3.0

4

4

4

750 --- 750/600

480

902

400

4

3 --- 3.5

3

3

3

750 --- 750/600

600

722

500

3

3 --- 3.0

4

4

4

750 --- 750/675

480

902

400

4

3 --- 3.5

3

3

3

750 --- 750/675

600

722

500

3

3 --- 3.0

4

4

4

DESCRIPTION:

DRAWING NO:

SHEET:

164201373---14

UPM OUTPUT-TO-SSBM CABLE AND

1 of 2

CONDUIT CONFIGURATIONS

NOTES:

1. * = Connections to output transformer, not UPM. Refer to applicable Powerware 9315 UPS Installation manual for UPS cable requirements

between the UPS and its output transformer.