SSBM CUSTOMER INTERFACE PANEL

5 of 6

164201373---4

A---17

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

Table J. Customer Interface Panel Inputs and Outputs

Terminal

Block

TB Pin #

Name

Description

1

CHANNEL A POWERNET --- HIGH

Channel A connection of PowerNet from UPS

2

CHANNEL A POWERNET --- LOW

Channel A connection of PowerNet from UPS

Modules. Used to control and monitor UPS

3

CHANNEL A POWERNET --- GND

Modules. Used to control and monitor UPS

modules.

4

NOT USED

TB1

5

NOT USED

TB1

6

CHANNEL B POWERNET --- HIGH

Channel B connection of PowerNet from UPS

7

CHANNEL B POWERNET --- LOW

Channel B connection of PowerNet from UPS

Modules. Used to control and monitor UPS

8

CHANNEL B POWERNET --- GND

Modules. Used to control and monitor UPS

modules.

9

EPO TO UPS MODULE --- RTN

Emergency Power Off control connections for

10

EPO TO UPS MODULE

Emergency Power Off control connections for

UPS modules

1

REMOTE EPO

Contacts used to activate remote EPO of SSBM

2

REMOTE EPO RTN

Contacts used to activate remote EPO of SSBM

and UPS.

3

NOT USED

4

NOT USED

TB2

5

BLDG ALARM 1

Programmable UPS alarm. Activated by a remote

TB2

6

BLDG ALARM 1 RTN

Programmable UPS alarm. Activated by a remote

contact closure. (See Note 1)

7

BLDG ALARM 2

Programmable UPS alarm. Activated by a remote

8

BLDG ALARM 2 RTN

Programmable UPS alarm. Activated by a remote

contact closure. (See Note 1).

9

BLDG ALARM 3

Programmable UPS alarm. Activated by a remote

10

BLDG ALARM 3 RTN

Programmable UPS alarm. Activated by a remote

contact closure.

1

BLDG ALARM 4

Programmable UPS alarm. Activated by a remote

contact closure Default is Go to Bypass

2

BLDG ALARM 4 RTN

contact closure. Default is Go to Bypass.

(See Note 2 and 3)

3

BLDG ALARM 5

Programmable UPS alarm. Activated by a remote

contact closure Default is Go to UPS

4

BLDG ALARM 5 RTN

contact closure. Default is Go to UPS.

(See Note 4)

TB3

5

BLDG ALARM 6

Programmable UPS alarm. Activated by a remote

TB3

6

BLDG ALARM 6 RTN

Programmable UPS alarm. Activated by a remote

contact closure. Default is on Generator.

7

NOT USED

8

NOT USED

9

NOT USED

10

NOT USED

NOTES:

1.

If the SSBM is equipped with an optional System Maintenance Bypass (SMB), Building Alarms #1

and #2 are used for the MIS and MBP breakers shown on the Monitor Panel Mimic and are

unavailable for customer use.

2.

If the SSBM is setup for Powerware Sync Control, Building Alarm #4 is used for the “Sync Control

Trouble” alarm and is unavailable for customer use.

3.

If the SSBM is setup for Powerware Hot-Tie Control, Building Alarm #4 is used for the programmed

control function “Hot-Tie Trouble” and is unavailable for customer use.

4.

If the SSBM is setup for Powerware Sync Control or Hot-Tie Control, Building Alarm #5 is used for

the programmed control function “Transfer to Bypass Disabled” and is unavailable for customer

use.