13--12

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

13.6.4 Customize Alarm Messages

If Customize Alarm Messages is selected from the Program Building Alarm menu,

you can select a custom message for a building alarm or disable a previously

enabled building alarm custom message. When this entry is selected, the following

menu is displayed:

Customize Alarm Messages
Enabled on Building Alarm Number(s)
2 3
Enter Building Alarm Number:

This example indicates that there are custom messages enabled for Building

Alarms 2 and 3. When a building alarm number is entered, the message being

used by the software is displayed (either a custom message or the default

message indicated by the list of enabled custom messages). If 1 was entered at the

prompt, the following will be displayed:

Building Alarm Active Message: Building Alarm 1 (default message)
Enter New Message or <CR> for No Change:

At this level you can enter a custom message, 30 characters maximum, to display

when Building Alarm 1 is activated. If a custom message is entered to activate the

building alarm, a custom message should also be entered to deactivate. After the

message or a carriage return is entered, the following is displayed:

Building Alarm Clear Message: Clear Building Alarm 1 (default message)
Enter New Message or <CR> for No Change:

At this prompt, the user should enter the custom message for the building alarm

deactivation state. When a message or a carriage return is entered, the following

will be displayed:

Enter E to Enable Custom Message
Enter D to Disable Custom Message
Enter <CR> for No Change
Enter Selection:

If an E is entered at the prompt, the custom messages will be used for the building

alarm. If a D is entered, the default messages will be used for the building alarm.