A---12

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

NOTE: 1. Accommodates one to eight UPMs. Four UPM system shown.

NOTE: 2. A bypass neutral feeder must be installed when the output neutral is used. If no

bypass neutral is installed, the output neutral is to be bonded to the chassis in the

SSBM through the minimum size copper conductor listed in Table H. In either case,

fully rated neutral conductors are to be run from the output of each UPM to the

neutral bus bar inside the SSBM.

Table H. Minimum Size Copper Bonding Jumper

SSBM Model

Wire Size (kcmil)

2500A

500

3000A

600

4000A

700

NOTE: 3. Refer to Section 1.1.4 for additional guidance for wiring and conduit installation.

NOTE:

4. The required neutral conductors must be spread as evenly as possible through

the available runbacks.

DESCRIPTION:

DRAWING NO:

3 of 3

SHEET:

ONELINE DRAWINGS OF TYPICAL PARALLEL

CAPACITY/REDUNDANT SYSTEM

164201373---3