10--1

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

Operating Instructions for the

Parallel Capacity/Redundant System

10.1

General Information --- Before You Start

The following procedures provide instructions for operating the Parallel

Capacity/Redundant System.

NOTE: 1. Before starting the Parallel Capacity/Redundant system ensure all

installation tasks are complete and a preliminary startup has been

performed by authorized service personnel. The preliminary startup

verifies all electrical interconnections to ensure the installation was

successful and the Parallel Capacity/Redundant system operates properly.

2. Refer to Chapter 9 of this manual for description of SSBM controls and

monitor panel functions.

3. Refer to the applicable Powerware9315 UPS Operation manual

provided with the UPMs, for UPM operating instructions.

10.2

Operation of SSBM with

Powerware 9315---200 thru 9315---500 UPMs

10.2.1 Initial Setup

1.

Ensure the Switchboard System Bypass Module (SSBM) circuit breakers are

manually charged and set as follows:

System Output Breaker (CBS)

---

OPEN

System Bypass Breaker (CBP)

---

OPEN

Backfeed Protection Breaker (FBP)

---

OPEN

Maintenance Isolation Breaker (MIS) ---

CLOSED (Optional)

Maintenance Bypass Breaker (MBP) ---

OPEN (Optional)

NOTE: When power is applied in the following step, circuit breakers CBS, CBP, and

FBP will charge, if not already charged.

2.

Close upstream UPM and SSBM Bypass input feeder circuit breakers.

3.

Observe SSBM monitor screen becoming active and Alarm and Notice

messages scrolling.