Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

9.6

Using the Menu Options

The UPS

menus allow you to display data in the information area to help you

monitor and control UPS operation. The following menus and options are

available:

Meters

Displays performance meters for the system or critical load.

Events

Displays the list of Active System Events and a historical log of

system events.

Statistics

Displays statistical information about UPS operations for the

battery, load, or line.

Graphics

Displays a real-time graphic representation of the flow of current

through the internal UPS components.

Setup

Allows you to configure the UPS communications port and set

the date and time for the time stamp.

9.6.1

System Meters Screen

Figure 9---3 shows the LCD screen as it appears when you first start the UPS. The

Meters menu is displayed in the menu box, with the System option highlighted. In the

information area, the system meters show their current readings.

Uninterruptible Power System

System Normal

Meters

System

Load Amps

Events Statistics Graphics Setup

Input

Output

Bypass

Battery

VAB

480

VBC

VCA

KW

379

KVA

399

IA

IB

IC

FREQ

60.0

PF

0.95

V

540

I

18

Meters

480

480

480

480

480

VAB

480

VBC

VCA

480

480

IA

IB

IC

361

361

361

IN

000

VAB

480

VBC

VCA

480

480

FREQ

60.0

KVA

300

KW

240

PF

0.80

Battery

48.5

Minutes

Versions

+

ALARM:

NONE

NOTICES: NONE

15 JUL 1998

09:25:42

Figure 9---3. System Meters Screen

(Typical for Powerware 9315---300 480/480V Unit)

The Input area shows the phase-to-phase voltage, frequency, and phase current of the

incoming utility, followed by the KVA, KW, and power factor measurements. The output

area shows the same information for the power being output by the UPS.
The Bypass area shows the phase-to-phase voltage of the bypass source. The Battery

area displays the DC voltage (V) and the DC current (I).