2--4

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

2.4

Installing the Powerware Static Switch

Your Switchboard System Bypass Module (SSBM) includes the Powerware static

switch shown below.

SSBM Current

Rating

Static Switch

Current Rating

Static Switch

Type

Static Switch

Manufacturer

Static Switch

Weight kg (lbs)

2500A

2500A

Fully Rated

Powerware

91 (200)

3000 to 4000A

4000A

Fully Rated

Powerware

227 (500)

2.4.1

Installing a Fully Rated Static Switch (2500A or 4000A)

WARNING:

The SSBM should be shut down prior to installing the static switch.

If the SSBM cannot be shut down, transfer the SSBM to Bypass and manually

open the FBP breaker prior to installing the static switch.

If the SSBM is supplied with a System Maintenance Bypass (SMB), transfer the

SSBM to Maintenance Bypass prior to installing the static switch.

Using an adequate lifting device, install the fully rated static switch in the same

manner as a drawout circuit breaker.

2.5

Installing SSBM or SMB Circuit Breakers

The SSBM and SMB are equipped with General Electric PowerBreakRII drawout

circuit breakers.

SSBM

Current Rating

Circuit Breaker

Current Rating

(100% Rated)

Circuit Breaker

Manufacturer

Circuit Breaker

Weight kg (lbs)

2500A/100 kAIC

2500A/100 kAIC

General Electric

110 (242)

3000A/65 kAIC

3000A/65 kAIC

General Electric

110 (242)

3000A/100 kAIC

3000A/100 kAIC

General Electric

110 (242)

4000A/65 kAIC

4000A/65 kAIC

General Electric

138 (304)

4000A/100 kAIC

4000A/100 kAIC

General Electric

138 (304)

2.5.1

Installing an SSBM or SMB Circuit Breaker

NOTE: The General Electric installation instructions and user’s guides noted below

are available at the GE Industrial Systems Publications Library website of

http://www.geindustrial.com/cwc/library.

Using an adequate lifting device, install the SSBM and SMB circuit breakers per

instructions in GE Document GEH---6271,

Installation Instructions for PowerBreak

t

II

Circuit Breakers, Draw-Out 800---4000 Ampere Frames.