2 redundant cbp mode (optional) – Powerware 9315s User Manual

Page 64

Advertising
background image

7--12

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

7.3.2

Redundant CBP Mode (Optional)

The Parallel Capacity/Redundant system can be protected against failure of the

CBP breaker to close if an electrically interlocked System Maintenance Bypass

(SMB) with Redundant CBP controls has been provided. The Redundant CBP

controls protect the critical load against power losses caused by CBP close failures

during manual or automatic operations.
Redundant CBP operations can be recognized by an alarm condition at the SSBM

and the following breaker conditions:

CBP

OPEN

CBS

OPEN

FBP

OPEN

MIS

CLOSED

MBP

CLOSED

CAUTION:

The critical load is not protected while the Parallel Capacity/Redundant

system is in Maintenance Bypass or Bypass mode.

Once Redundant CBP operation has occurred, the SSBM must be isolated to allow

CBP breaker maintenance without impact on the system’s critical load. To achieve

SSBM isolation, the Redundant CBP controls have been interlocked with the

System Maintenance Bypass controls. To exit from Redundant CBP operation, the

SMB control switch must be turned to the

TO MAINT position. This action opens

the UPS system MIS breaker and places the the UPS system fully into Maintenance

Bypass mode.
After the CBP breaker has been repaired, the UPS system can be transferred from

Maintenance Bypass mode to Bypass mode as described above.

Figure 7---7 shows the path of electrical power through the Parallel

Capacity/Redundant system when operating in Maintenance Bypass mode.

Advertising