DESCRIPTION:

DRAWING NO:

SHEET:

164201373---7

REMOTE EMERGENCY POWER OFF

1 of 2

A---26

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

1.

The Remote EPO feature shuts down the UPS modules, opens all breakers in the

Switchboard System Bypass Module and isolates power from your critical load. Local

electrical codes may also require tripping upstream protective devices to the UPS

modules.

2.

To open all UPM breakers, a separate twisted pair of wires and an EPO Kit (sold

separately) must be installed to the modules from the SSBM.

3.

Use Class 1 wiring methods (as defined by the NEC) for control wiring. Install the control

wiring in separate conduit from the power wiring. The wire should be rated at 24 volts,

1 amp minimum.

4.

Refer to Table N of this drawing and to applicable chapters for information about installing

control remote EPO.

5.

Refer to drawings 164201373---4 and 164201373---13 for location of the Customer Interface

panel and drawing 164201373---4 for the terminal block location on the Customer Interface

Panel.

Table N. Remote EPO

1

2

REMOTE

EPO

SWITCH

TWISTED

WIRES (2)

TB2

Remote EPO switch rating is 24 VDC.

1 amp minimum if supplied by user.

NOTE: This switch must be a dedicated switch, and not

tied into any other circuits.