Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

Redundant CBP Operation:

The Redundant CBP controls protect the critical load against power losses caused

by CBP breaker close failures during manual or automatic operations.

1.

Redundant CBP operations can be recognized by an alarm condition at the

SSBM and the following breaker conditions:

CBP

Open

CBS

Open

FBP

Open

MIS

Closed

MBP

Closed

2.

Once Redundant CBP operation has occurred, the SSBM should be isolated

to allow CBP breaker maintenance without impact on the system’s critical load.

To achieve SSBM isolation and to exit from Redundant CBP operation, turn the

SMB key switch to the left (TO MAINTENANCE) momentarily. This action will

open the UPS system’s MIS breaker and place the UPS system fully into

Maintenance Bypass mode.

Note: If the CBP breaker failure can be repaired without SSBM isolation,

complete the CBP repairs and then, proceed to step 3 below.

3.

After the CBP breaker has been repaired, the UPS system can be transferred

from

Maintenance Bypass mode to Bypass mode as described above.