Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

To install a Remote EPO control:

1.

Securely mount the Remote EPO station. Recommended locations include

operator’s consoles or exit doors.

2.

Install wiring from the Remote EPO station using ½-in. conduit through the

cable entry panels on the top of the SSBM.

3.

Connect the Remote EPO wiring as shown in Tables 3---1 and 3---2:

Table 3---1. Remote EPO Wire Terminations

From Remote

EPO Station(s)

To Customer Interface

Panel in SSBM

Remarks

TB1---4

TB2---1

Twisted wires (2)

TB1---5

TB2---2

Twisted wires (2)

14---18 gauge

Table 3---2. Remote EPO

1

TB2

2

REMOTE

EPO

SWITCH

TWISTED

WIRES (2)

Remote EPO switch rating is 24 VDC.

1 Amp minimum if supplied by user.

NOTE: This switch must be a dedicated

switch not tied into any other circuits.

4.

If you are installing multiple Remote EPO stations, wire additional stations in

parallel with the first Remote EPO.

5.

If required, install ½-in. conduit and wiring from the Remote EPO station to trip

circuitry of upstream protective devices. A normally open contact is provided,

as shown in Table 3---2. Remote EPO switch wiring must be in accordance

with UL Class 1 requirements.

6.

Secure the SSBM by reversing all steps taken to prepare it for Remote EPO

installation.