Powerware 9315s User Manual

Page 45

Advertising
background image

5--3

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

4.

Connect RIM wiring to the terminal block using the terminations shown in

Table 5---1.

Table 5---1. RIM Wire Terminations

From RIM A

To SSBM

Remarks

TB1---4

TB3---1

TWISTED WIRES (4)

TB1---5

TB3---2

TWISTED WIRES (4)

1---2 TURNS PER

TB1---6

TB3---3

1 2 TURNS PER

3 INCHES

TB1---7

TB3---4

From RIM B (if used)

To SSBM

Remarks

TB1---4

TB3---5

TWISTED WIRES (4)

TB1---5

TB3---6

TWISTED WIRES (4)

1---2 TURNS PER

TB1---6

TB3---7

1 2 TURNS PER

3 INCHES

TB1---7

TB3---8

5.

Contact your local field service office for verification and testing of the RIM

and its connections prior to making connections to J1---J4.
You can order interface cables separately for connecting to the 15-Pin D-Sub

Connectors.

6.

Repeat steps 1 through 5 for each RIM you are installing.

7.

If you are installing an RMP or SCM in addition to an RIM, proceed to Chapter

4 or 6, respectively; otherwise, secure the SSBM by reversing the steps

contained in procedure “To Prepare the SSBM for Wiring to an RMP, RIM,

SCM, or Remote EPO” of Chapter 2.