Powerware 9315s User Manual

Page 111

Advertising
background image

11--3

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

The RMP contains a local horn and the following backlit status indicators:

SYSTEM NORMAL

The UPS is energized (either with utility power

or battery backup) and is supplying

conditioned power to the critical load.

NO REDUNDANCY

This indicator applies only to parallel systems

when one cabinet is not functioning. This

feature is not available on this system.

ON GENERATOR

This alarm means that the UPS input and

bypass are being supplied by the power from

the generator, instead of from the utility power.

ON BYPASS

The bypass source is supplying the critical

load. Usually this means that the UPS is not

energized. The load is not protected in Bypass

mode, and a horn sounds after 30 seconds.
UPS ALARM

The UPS system is issuing an alarm.

Conditions that affect the current UPS mode

are indicated by the alarm lamps and horn on

the UPS.
ON BATTERY

The UPS battery backup is supplying the

critical load. The utility power is either

interrupted or out of specification. The

SYSTEM NORMAL indicator is also lit.
BYPASS UNAVAILABLE

The UPS system is in Normal mode, but

a bypass source is not within specification.

A horn sounds after 30 seconds.

SHUTDOWN IMMINENT

The UPS is preparing to shut down because

the UPS is in Battery mode and the DC voltage

is approaching its low limit.

This light is accompanied by an audible alarm

horn.

Advertising