2 to install an rmp – Powerware 9315s User Manual

Page 41

Advertising
background image

4--3

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

NOTE: Before installing an RMP, be sure you have prepared the SSBM according to

the instructions in Chapter 2.

4.2

To install an RMP:

1.

Securely mount the RMP(s).

2.

Install wiring from the RMP using ½-in. conduit through the cable entry panels

in the top of the SSBM control section (refer to the enclosed switchboard

vendor drawings for the location of the conduit landing plate).

3.

In the spare parts kit, locate the RMP adapter cable assembly

(see Figure 4---2). Mate the DB---9 connector on the back of the terminal block

to the DB---9 connector (Port 1) on the Customer Interface Panel of the SSBM

(refer to Drawing 164201373---4 in Appendix A). Use two screws from the

spare parts kit to secure the terminal block bracket to the Customer Interface

Panel.

Connect to

Port 1 (DB---9) on

Customer Interface Panel

TERMINAL

BLOCK

FUSE

(TB3)

Figure 4---2. Terminal Block Bracket