10.3.7 Using the UPM EMERGENCY UPM OFF Pushbutton

NOTE: The UPM EMERGENCY UPM OFF pushbutton will only interrupt the ability

for that module to deliver power to the critical bus. The redundant modules

continue to support the critical load.

Emergency UPM shutdown is initiated by the covered, red UPM

EMERGENCY

UPM OFF pushbutton on the UPM Monitor Panel. This pushbutton is protected by

a clear plastic shield to prevent accidental activation. In an emergency, you can

press this pushbutton to instantaneously open all UPM breakers and interrupt UPM

output. The UPM remains locked off until you reset the

EMERGENCY UPM OFF

pushbutton.
To restart the UPS after pressing the

EMERGENCY UPM OFF pushbutton, follow

the procedure “Resetting the UPM after Shutdown” of this chapter before starting

the UPS.

NOTE: The UPM REMOTE EMERGENCY LOAD OFF (REPO) functions in the same

way as the UPM

EMERGENCY UPM OFF pushbutton on the UPM Monitor

panel.

10.3.8 To Use the UPM EMERGENCY UPM OFF Pushbutton

1.

Raise the clear plastic shield covering the red

EMERGENCY UPM OFF

pushbutton on the UPM Monitor Panel.

2.

Press the

EMERGENCY UPM OFF pushbutton.

UPS breakers CB1 and CB3 and Battery breaker CB2 (MBB) open. The

EMERGENCY UPM OFF

PUSH TO RESET pushbutton on the UPM Control Panel

pops out. The UPM shuts down.

10.3.9 Resetting the UPM after an EMERGENCY UPM Shutdown

CAUTION:

Do not attempt to restart the UPM after Emergency UPM Shutdown until the

cause of the emergency has been identified and cleared.

The EMERGENCY UPM OFF

PUSH TO RESET pushbutton is a small white button

on the UPM Control Panel. The

PUSH TO RESET pushbutton pops out when the

EMERGENCY UPM OFF pushbutton on the Monitor Panel is activated.

To reset the UPM:

1.

Press the EMERGENCY UPM OFF

PUSH TO RESET pushbutton until it clicks

in and remains recessed.

2.

The UPM is now reset. To restart the UPM, follow the procedure in this

chapter, “Restarting a Single UPM.”