The

Switchboard System Bypass Module (SSBM) and UPMs of the Parallel

Capacity/Redundant system are shipped on separate pallets. Use a forklift or pallet

jack to move the packaged cabinets to the installation site, or as close as possible

to the site, before unloading from the pallet.

This is the basic sequence of the installation steps:

1.

Create an installation plan for the Parallel Capacity/Redundant system

(Chapter 1).

2.

Prepare your site for the Parallel Capacity/Redundant system (Chapter 1).

3.

Inspect, unpack, and unload the SSBM (Chapter 1).

4.

Inspect, unpack, and unload the UPMs (refer to the applicable

Powerware

9315 Installation manual provided with the UPM).

5.

Wire the system (refer to Chapter 2 and the applicable

Powerware9315

Installation manual provided with the UPM).

6.

Install features, accessories, and/or options, as applicable (Chapter 3).

7.

Complete the Installation Checklist (Chapter 2).

8.

Have authorized service personnel perform preliminary operational checks and

startup.

NOTE: Startup and operational checks should be performed only by authorized

service personnel. This service is usually offered as part of the sales

contract for your Parallel Capacity/Redundant system. Contact service in

advance (usually a two week notice is required) to reserve a preferred

startup date.

1.1.1

Creating an Installation Plan

Before beginning to install the Parallel Capacity/Redundant system, read and

understand how this manual applies to the system being installed. Use the

procedures and illustrations in the following chapters to create a logical plan for

installing the system. It is important to note that UPM installation procedures are

contained in the applicable

Powerware9315 Installation manual provided with the

UPMs. First understand how to install the UPMs before installing the SSBM. The

information in Chapter 2 of this manual provides a guide to installation of the SSBM

to the UPMs.