10--15

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

10.4

Operation of the Optional System Maintenance Bypass

(SMB)

The optional System Maintenance Bypass (SMB) is available with electrical

controls. The SMB electrical controls are available with or without Redundant

CBP controls. Operations of each configuration is detailed below.

CAUTION:

The critical load is not protected while the Parallel Capacity/Redundant

system is in Maintenance Bypass or Bypass mode.

10.4.1 Operation with Electrical Controls

NOTE: Refer to Drawing 164201373---11 in Appendix A for the location of the

Maintenance Bypass key switch.

Transfer to Maintenance Bypass:

1.

Ensure power is supplied to the MBP breaker input before attempting transfer

to maintenance bypass.

2.

On SSBM, ensure that SSBM CBS breaker is open or system is not on inverter.

3.

On SSBM, turn the Maintenance Bypass key switch to the left

(TO MAINTENANCE) momentarily.

4.

Observe MBP closes and MIS opens. System is now on maintenance bypass.

5.

To shutdown SSBM and UPMs, follow procedure under

SSBM Shutdown to

Bypass.

6.

On SSBM, open CBP and FBP breakers.