Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

11.5

Relay Interface Module

An optional Relay Interface Module (RIM) uses relay contact closures to indicate

the operating status and alarm condition of the Parallel Capacity/Redundant

system . A maximum of two monitoring accessories (RMPs, RIMs, or SCMs) can

be installed. See Table 11---1 for the number of accessories permitted. Figure

11---2 shows the RIM with its four 15-pin connectors labeled J1 through J4.

Figure 11---2. Relay Interface Module

The RIM can provide these signals:

UPS AVAILABLE

(pins 1 and 12) Contacts are closed when the UPS is

offline.

UPS OFF LINE

(pins 3 and 13) Contacts are closed when the UPS is

operating in Normal mode.

UTILITY FAILURE

(pins 6 and 15) Contacts are closed when Utility Failure is

detected.

BATTERY WEAK

(pins 5 and 14) Contacts are closed when approximately

2 minutes of battery time is remaining, before the critical

load is lost.