2 to install a supervisory contact module – Powerware 9315s User Manual

Page 48

Advertising
background image

6--2

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

6.2

To install a Supervisory Contact Module:

1.

Securely mount the SCM.

2.

Install wiring from the SCM using ½-in. conduit through the cable entry panels

in the top of the SSBM control section (refer to the enclosed switchboard

vendor drawings for the location of the conduit landing plate).

3.

If not already installed, locate the RMP adapter cable assembly (see

Figure 6---2) in the spare parts kit. Mate the DB---9 connector on the back of

the terminal block to the DB---9 connector (Port 1) on the Customer Interface

Panel of the SSBM (refer to Drawing 164201373---4 in Appendix A). Use two

screws from the spare parts kit to secure the terminal block bracket to the

Customer Interface Panel.

TERMINAL

BLOCK

FUSE

(TB3)

Connect to

Port 1 (DB---9) on

Customer Interface Panel

Figure 6---2. Terminal Block Bracket