Bc d e, Ab c d e – Powerware 9315s User Manual

Page 158

Advertising
background image

A

DESCRIPTION:

DRAWING NO:

INSTALLATION NOTES

SHEET:

164201373---1

NOTE:

Callout letters

and

map to drawing #164201373---3

, ,

B

C

D

E

A

B

B C

,

D

E

,

1 of 6

A

B

C

D

E

A---2

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

Table A. INPUT/OUTPUT Ratings & External Wiring Requirements for

Powerware 9315 Switchboard System Bypass Module (SSBM):3P3W

(Output Neutral Not Used)

Units

Rating

Ratings

SSBM Model

2500

3000

4000

g

Maximum Amps

2500

3000

4000

AC

INPUT

(Note 5)

AC Input from UPS to SSBM CBS Breaker

Minimum conductor size, 3∅, (1) neutral, (1) gnd

(number per ∅ and neutral)

AWG or

kcmil(ea)

Refer to Table R for minimum

conductor sizes.

AC

INPUT

AC Input to SSBM Bypass

Full Load Current minimum conductor size,

3∅, (1) gnd (number per ∅)

AWG or

kcmil(ea)

500

(6)

500

(7)

500

(9)

AC

INPUT

(Note 2)

AC Input to optional SMB Bypass

Full Load Current minimum conductor size,

3∅, (1) gnd (number per ∅)

AWG or

kcmil(ea)

500

(6)

500

(7)

500

(9)

AC

OUTPUT

AC Output from SSBM to Load Bank

Full Load Current minimum conductor size,

3∅, (1) gnd (number per ∅)

AWG or

kcmil(ea)

500

(6)

500

(7)

500

(9)

AC

OUTPUT

AC Output from SSBM or optional SMB to

Critical Load

Full Load Current minimum conductor size,

3∅, (1) gnd (number per ∅)

AWG or

kcmil(ea)

500

(6)

500

(7)

500

(9)

Table B. INPUT/OUTPUT Ratings & External Wiring Requirements for

Powerware 9315 Switchboard System Bypass Module (SSBM):3P4W

(Output Neutral Used)

Units

Rating

Ratings

SSBM Model

2500

3000

4000

g

Maximum Amps

2500

3000

4000

AC

INPUT

(Note 5)

AC Input from UPS to SSBM CBS Breaker

Minimum conductor size,

3∅, (1) neutral, (1) gnd (number per ∅ and neutral)

AWG or

kcmil(ea)

Refer to Table R for minimum

conductor sizes.

AC

INPUT

AC Input to SSBM Bypass

Full Load Current minimum conductor size,

3∅, (1) neutral, (1) gnd (number per ∅ and neutral)

AWG or

kcmil(ea)

500

(7)

600

(8)

600

(11)

AC

INPUT

(Note 12)

AC Input to optional SMB Bypass

Full Load Current minimum conductor size,

3∅, (1) neutral, (1) gnd (number per ∅ and neutral)

AWG or

kcmil(ea)

500

(7)

600

(8)

600

(11)

AC

OUTPUT

AC Output from SSBM to Load Bank

Full Load Current minimum conductor size,

3∅, (1) neutral, (1) gnd (number per ∅ and neutral)

AWG or

kcmil(ea)

500

(7)

600

(8)

600

(11)

AC

OUTPUT

AC Output from SSBM or optional SMB to

Critical Load

Full Load Current minimum conductor size,

3∅, (1) neutral, (1) gnd (number per ∅ and neutral)

AWG or

kcmil(ea)

500

(7)

600

(8)

600

(11)