Bc d e, Ab c d e – Powerware 9315s User Manual

Page 158

Advertising
background image

A

DESCRIPTION:

DRAWING NO:

INSTALLATION NOTES

SHEET:

164201373---1

NOTE:

Callout letters

and

map to drawing #164201373---3

, ,

B

C

D

E

A

B

B C

,

D

E

,

1 of 6

A

B

C

D

E

A---2

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

Table A. INPUT/OUTPUT Ratings & External Wiring Requirements for

Powerware 9315 Switchboard System Bypass Module (SSBM):3P3W

(Output Neutral Not Used)

Units

Rating

Ratings

SSBM Model

2500

3000

4000

g

Maximum Amps

2500

3000

4000

AC

INPUT

(Note 5)

AC Input from UPS to SSBM CBS Breaker

Minimum conductor size, 3, (1) neutral, (1) gnd

(number per and neutral)

AWG or

kcmil(ea)

Refer to Table R for minimum

conductor sizes.

AC

INPUT

AC Input to SSBM Bypass

Full Load Current minimum conductor size,

3, (1) gnd (number per ∅)

AWG or

kcmil(ea)

500

(6)

500

(7)

500

(9)

AC

INPUT

(Note 2)

AC Input to optional SMB Bypass

Full Load Current minimum conductor size,

3, (1) gnd (number per ∅)

AWG or

kcmil(ea)

500

(6)

500

(7)

500

(9)

AC

OUTPUT

AC Output from SSBM to Load Bank

Full Load Current minimum conductor size,

3, (1) gnd (number per ∅)

AWG or

kcmil(ea)

500

(6)

500

(7)

500

(9)

AC

OUTPUT

AC Output from SSBM or optional SMB to

Critical Load

Full Load Current minimum conductor size,

3, (1) gnd (number per ∅)

AWG or

kcmil(ea)

500

(6)

500

(7)

500

(9)

Table B. INPUT/OUTPUT Ratings & External Wiring Requirements for

Powerware 9315 Switchboard System Bypass Module (SSBM):3P4W

(Output Neutral Used)

Units

Rating

Ratings

SSBM Model

2500

3000

4000

g

Maximum Amps

2500

3000

4000

AC

INPUT

(Note 5)

AC Input from UPS to SSBM CBS Breaker

Minimum conductor size,

3, (1) neutral, (1) gnd (number per and neutral)

AWG or

kcmil(ea)

Refer to Table R for minimum

conductor sizes.

AC

INPUT

AC Input to SSBM Bypass

Full Load Current minimum conductor size,

3, (1) neutral, (1) gnd (number per and neutral)

AWG or

kcmil(ea)

500

(7)

600

(8)

600

(11)

AC

INPUT

(Note 12)

AC Input to optional SMB Bypass

Full Load Current minimum conductor size,

3, (1) neutral, (1) gnd (number per and neutral)

AWG or

kcmil(ea)

500

(7)

600

(8)

600

(11)

AC

OUTPUT

AC Output from SSBM to Load Bank

Full Load Current minimum conductor size,

3, (1) neutral, (1) gnd (number per and neutral)

AWG or

kcmil(ea)

500

(7)

600

(8)

600

(11)

AC

OUTPUT

AC Output from SSBM or optional SMB to

Critical Load

Full Load Current minimum conductor size,

3, (1) neutral, (1) gnd (number per and neutral)

AWG or

kcmil(ea)

500

(7)

600

(8)

600

(11)