DESCRIPTION:

DRAWING NO:

5 of 6

INSTALLATION NOTES

SHEET:

164201373---1

A---6

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

12.

The 100% rated bypass input overcurrent protection and bypass input disconnect switch

are to be provided by the user. Table E lists the maximum rating for output circuit breakers

satisfying the criteria for both. Rating is based on 100% of output current for a 100%

breaker.

Table E. Maximum Bypass Input Circuit Breaker Ratings

Powerware 9315 Switchboard System Bypass module

SSBM Model

Powerware 9315 Switchboard System Bypass module

2500

3000

4000

SSBM Bypass

2500

3000

4000

SMB Bypass

2500

3000

4000

13.

The breakers CBS, CBP, FBP, MBP (optional) and MIS (optional) have AT trip ratings and a

maximum Amp Interrupting Capability (KAIC) as shown in Table F.

Table F. SSBM Breaker Trip Ratings and Amp Interrupting Capability

P

9315 S it hb

d S t

B

SSBM Model

Powerware 9315 Switchboard System Bypass

module

2500

3000

4000

All Models

module

Trip Rating

KAIC

SSBM and SMB

N/A

3000

4000

65

SSBM and SMB

2500

3000

4000

100

14.

The 100% rated output overcurrent protection and output disconnect switch are to be

provided by the user. Table G lists the maximum rating for output circuit breakers

satisfying the criteria for both. Rating is based on 100% of output current for a 100%

breaker.

Table G. Maximum Output Circuit Breaker Ratings

Powerware 9315 Switchboard System Bypass module

SSBM Model

Powerware 9315 Switchboard System Bypass module

2500

3000

4000

SSBM

2500

3000

4000

SMB

2500

3000

4000

15.

In the Parallel Capacity/Redundant System, each UPS module, Switchboard System

Bypass Module (SSBM), SSBM breakers, and optional equipment are crated separately

for shipping.

16.

Do not tilt cabinets more than

¦

10˚during handling.

17.

Dimensions are in millimeters (inches).