Wining configurations, 1 important preliminary checks – KYORITSU 6310 Instruction Manual User Manual

Page 130

Advertising
background image

5.1 Important Preliminary Checks KEW6310

5.1

KEW6310

5. Wining Configurations

5.1 Important preliminary checks

DANGER

● Do not make measurements on a circuit in which electrical potential exceeds AC600V.
● Connect the Power cord to a socket outlet. Never connect it to the socket outlet of AC240V or more

.

● The Clamp sensor, Voltage test leads and Power cord are to be connected to the instrument first.
● The Voltage test leads or Clamp sensors should not be connected to the input terminals of the instrument

if not required for measurement.

● The instrument should always be connected on the downstream side of a circuit breaker, which is safer

than the upstream side.

● Do not open-circuit the secondary side of a supplementary CT while it is energized because of the high

voltage generated at the secondary side terminals.

● Be careful to avoid short-circuiting the power line with the un-insulated part of the voltage test probes

during the setting up of the instrument.

Transformer jaw tips are designed in such a way to avoid

short-circuiting. If the circuit under test has exposed conductive parts, extra care should be taken to
minimize the possibility of shorting.


WARNING


● To avoid possible electric shock and short-circuit, always turn off the line under test when setting up the

instrument.

● Do not touch the un-insulated tip of Voltage test probes. The use of safety insulted gloves is recommended.


Direction for correct measurements


● Proper setting of wiring configuration should be made.
● Ensure that the arrow mark on the clamp sensor points towards to load side.









* Reverse clamping switches the symbols (+/-) for active power [P].

Arrow mark: Points
towards load side.

Load

Source