KEW6310 4.2.2 Measurement Setting (QUALITY-Transient Measurement)

KEW6310

4.50

Setting for hysteresis

1 ~ 10% (can be set by 1%)

* Default value (or after system reset) : 5%

* Setting procedure is same to that for Hysteresis Setting for Swell, Dip, Int measurement.

Refer to the procedure described in the preceding pages.

Setting for trigger point

Past: 1 ~ 200 (can be set by 1)

Next : 200 ~ 0 (can be set by 1)

* Default value (or after system reset) : 100

* Trigger to start and stop recording when a preset threshold exceeded will be decided based on
the number of recorded data.

* Setting procedure is same to that for Trigger Point Setting for Swell, Dip, Int measurement.
Refer to the procedure described in the preceding pages.