3 voltage test leads and clamp sensor connection, Voltage test leads and clamp sensor connection – KYORITSU 6310 Instruction Manual User Manual

Page 37

Advertising
background image

KEW6310 3.3 Voltage test leads and Clamp sensor connection

KEW6310

3.10

3.3 Voltage test leads and Clamp sensor connection

Check the followings before connection.

DANGER

● Use only the Voltage test leads supplied with this instrument.
● Use the dedicated Clamp sensor for this instrument, and confirm that the measured current rating of the
Clamp sensor is not exceeded.
● Do not connect all the Voltage test leads or Clamp sensors unless required for measuring the parameters
desired.
● Connect the test leads and sensors to the instrument first, and only then connect them to the circuit
under

test.

● Never disconnect the Voltage test leads and sensors while the instrument is in use.

WARNING

● Confirm that the instrument is powered off, and then connect the Power cord.
● Connect the Power cord to the instrument first. Cord to be firmly inserted.
● Never attempt to make measurement if any abnormal conditions such as abnormal conditions are noted,
such as a broken Cover and exposed metal parts.

Voltage test leads and Clamp sensor connection

Follow the procedure below, and connect the Voltage test leads and Clamp sensors.

1 Confirm that the instrument is powered off.
2 Connect the appropriate Voltage test leads to the Voltage input terminal on the instrument.
3 Connect the appropriate Clamp sensors to the Current input terminal on the instrument. Match the direction of

the arrow mark indicated on the output terminal of the clamp sensor and the mark on the Current input
terminal on the instrument.

* Number of Voltage test leads and Clamp sensors to be used depends on the wiring configuration under
test. For further details, refer to “5.2 Basic Wiring Configuration” in this manual.

Match the arrow marks.