KEW6310 11.6.1 Power quality - Display(Flicker)

KEW6310

11.34

Measurement screen

Displayed parameters

Details

Time left

Counted down until a Pst calculation completes.

V

Avg voltage in 1 sec.

f

Refreshed at every 1 min.

Pst(1min.)

Pst is displayed at every 1 min.It takes time to calculate Pst.The value displayed

here before a calculation completes is just for reference.

Pst

Pst is calculated and displayed at every 10 min.

Plt

Calculated cased on the latest 12 Pst values.(data in 2 hours)

Max Pst

Max Pst(short time intensity) through a beginning to the end of measurement is
displayed.
It is refreshed every time when the max values is exceeded.

Max Plt

Max Plt(long time intensity) through a beginning to the end of measurement is
displayed.
It is refreshed every time when the max value is exceeded.

Max Pst/Max Plt