KEW6310 11.6.1 Power quality - Display(Flicker)
KEW6310
11.34
Measurement screen
Displayed parameters
Details
Time left
Counted down until a Pst calculation completes.
V
Avg voltage in 1 sec.
f
Refreshed at every 1 min.
Pst(1min.)
Pst is displayed at every 1 min.It takes time to calculate Pst.The value displayed
here before a calculation completes is just for reference.
Pst
Pst is calculated and displayed at every 10 min.
Plt
Calculated cased on the latest 12 Pst values.(data in 2 hours)
Max Pst
Max Pst(short time intensity) through a beginning to the end of measurement is
displayed.
It is refreshed every time when the max values is exceeded.
Max Plt
Max Plt(long time intensity) through a beginning to the end of measurement is
displayed.
It is refreshed every time when the max value is exceeded.
Max Pst/Max Plt