11.4.3 Power quality – Saving procedure (Inrush current measurement) KEW6310

11.23

KEW6310

3

Manually start saving data, or stand-by screen (WAIT) appears if saving start date and time

has been specified.


4

Saving starts and the LED status indicator lights up.

No setting change can be made during data saving. Press the

F4

Key to check the settings.

5

Press the

F1

Key to stop measurement. (At measurements with Timer function activated, this

Key activates in the same way.)

6

Measurement will end and the LED status indicator goes off.

.

Flashes.

File name for saving data is displayed.

Flashes.

Destination to save data will be

highlighted and flashes in red.

File name for saving data is displayed.