Setting for unbalance rate measurement, Setting for interval, Setting for output threshold – KYORITSU 6310 Instruction Manual User Manual

Page 94

Advertising
background image

4.2.2 Measurement Setting (QUALITY-Voltage Unbalance Ratio KEW6310

4.53

KEW6310

Setting for unbalance rate measurement


For the details of Voltage Unbalance Rate Measurement, refer to “11.5 Unbalance Rate” in this manual.

Setting Items

Interval :

set

interval time

Output threshold

: set threshold for the output of voltage unbalance rate

Setting for interval


* Default value (or after system reset) : 30 min
* Setting procedure is same to that for interval Setting for W/ Wh/ DEMAND.Refer to the procedure described in

the preceding pages.

Setting for output threshold

1 ~ 20% (can be set by 0.1%)

* Default value (or after system reset) : 3%

1

Press the

Cursor

Keys and select [Output Threshold], and then press the

ENTER

Key.

2

Press the

Cursor

Keys and alter values, and then press the

ENTER

Key.

Box with

▲▼

mark appears

at the rightmost digit.

Selected output threshold

is displayed.