Setting for transient – KYORITSU 6310 Instruction Manual User Manual

Page 80

Advertising
background image

KEW6310 4.2.2 Measurement Setting (QUALITY-Swell, Dip, Int Measurement)

4.39

KEW6310

Setting for Transient

Voltage Range

70~150V

151~300V

301~600V

601~1000V

Transient
(on 1V basis)

50~310Vpeak 90~630Vpeak

170~1270Vpeak

340~2000Vpeak

* Default value (or after system reset) : 210V
* Vrms value (Vpeak divided by √2) is automatically calculated when Vpeak is set.

1

Press the

Cursor

Keys and select [Transient], and then press the

ENTER

Key.

2

Press the

Cursor

Keys and alter the values, and press the

ENTER

Key

to fix it.

Box with

▲▼

mark appears

at the rightmost digit.

Selected threshold value is

displayed. Value displayed in
parenthesis is a Threshold value
divided by √2.