KEW6310 8.1.1 Demand Measurement – Display Screen

KEW6310

8.2

Measurement screen

Displayed
parameters

Details

Remaining time
(time left)

Demand interval is counted down.

Target value

Should be set for each measurement.

Predicted value

Predicted demand value (average power) when preset demand interval elapses
under present load.
(Present value) x (Preset interval)
(Elapsed time)
* Integration and calculations are done as time elapses.

Present value

Demand value (average power) within a demand interval.
“WP+ x 1 hour”

Interval

* Integration and calculations are done as time elapses.

Max demand

Max demand recorded in a measuring period is displayed. Displayed value will be
refreshed if any higher demand is detected.

Remaining time (time left)/ Target value/ Predicted value / Present value