KEW6310 4.2 .2 Measurement Setting (QUALITY-Swell, Dip, Int Measurement)

4.37

KEW6310

QUALITY

Press the

F4

Key at Measurement setting screens to move to the QUALITY setting screen.

Access to “QUALITY” from Measurement Setting Tab, and press
the

Cursor

Keys and select : Swell / Dip / Int, Transient, Inrush

current, Unbalance rate, Capacitance calculation and Flicker
measurement*.

* Flicker measurement function is only available with ver.2.00 or later.

Setting for Swell / Dip / Int Measurement

For the details of Swell / Dip / Int measurement, refer to “11.2 Swell / Dip / Int measurement” in this manual.

Setting Items

Interval

*2

: set interval time

Reference Voltage

*1

: set a standard voltage (70 ~ 1000V)

Transient

*2

: set Vpeak against Voltage Range(50~2000Vpeak)

Swell

*1

: set a threshold value greater than the reference voltage (100 ~ 200%)

Dip

*1

: set a threshold value smaller than the reference voltage (5 ~ 100%)

Int

*1

: set a threshold value smaller than the reference voltage (5 ~ 98%)

Hysteresis

: set a hysteresis for Swell / Dip / int (1 ~ 10%)

Trigger Point

: set the number of data save point prior to / following an event of trigger

* Voltage value is automatically calculated when setting percentages for Swell / Dip / Int / Hysteresis.
*1 Each values should be;

-

(Int + Hysteresis) < (Dip)

-

(Dip + Hysteresis) < (Swell)

*2 Flicker measurement function is only available with ver.2.00 or later.