5-20

Using the I/O

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

2. In the Chassis Type column, set the chassis type to match the chassis

being used.

For this example, the 1771-A1B (4 slots) is selected.

3. In the I/O Channel column, right-click the Local cell and choose

Display Chassis to display the Chassis configuration screen.

4. In the Module Type column, right-click the cell that corresponds with

the slot row in which the 1771-SDN scanner physically resides (for this
example, Slot 0) and choose Insert Module to display the Edit Module
screen.

5. In the Edit Module screen, select ‘1771-SDN - DeviceNet Scanner

Module’.

6. Click OK.

The 1771-SDN scanner should now appear in the Module Type column
in the appropriate slot row as shown in the example below.

7. Right-click the ‘1771-SDN’ cell and choose Display Module to display

the Enter Module Addresses screen.

a. In the Enter Module Addresses screen, enter unique block transfer

read and write control block addresses in the Address column.

For this example, BT11:0 is used for the block transfer read and
BT11:1 is used for the block transfer write.