6-22

Using Explicit Messaging

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

Table 6.K Example Single Write Response Data

Figure 6.24 Example Single Write Response Data File

PLC-5 Controller Example to Read Multiple Parameters

A scattered read message is used to read the values of multiple parameters.
Up to 19 parameters can be read. This read message example reads the
values of these five parameters in a PowerFlex 7-Class drive:

• Parameter 001 - [Output Freq]

• Parameter 003 - [Output Current]

• Parameter 006 - [Output Voltage]

• Parameter 012 - [DC Bus Voltage]

• Parameter 017 - [Analog In2 Value]

Address

Value

Description

Hex.

(1)

(1)

In RSLogix 5 software, leading zeros are not displayed in data file addresses. For example, ‘0000’ in address

N30:71 is shown as ‘0’.

Dec.

N30:70

0101

257

TXID = 01, Status = 01 (successful)

N30:71

0000

0

Port = 00, Size = 00 bytes

N30:72

9001

-28671

Service = 90 (successful), Address = 01 (Node)