Using Explicit Messaging

6-43

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

Table 6.V Example Scattered Write COP Request Data

Figure 6.48 Example Scattered Write COP Request Data File

Address

Value

Description

Hex.

(1)

(1)

In RSLogix 5 software, leading zeros are not displayed in data file addresses. For example, ‘0024’ in address

N30:1 is shown as ‘24’.

Dec.

N30:0

0101

257

TXID = 01, Command = 01 (execute)

N30:1

0024

36

Port = 00, Size = 36 bytes

(3)

(3)

The maximum number of bytes that can be entered is 120 (78 Hex.), which represents 19 parameters. The

number of required bytes always includes 2 for the Class, 2 for the Instance, 2 for the Attribute, 2 for each

parameter being written to, and 4 for each parameter value (2 bytes for the Least Significant Word and 2 bytes

for the Most Significant Word). For this example where 5 parameters are being written to, a value of 36 bytes is

required.

N30:2

4C01

19457

Service = 4C (Set_Attribute_Single), Address = 01 (Node)

N30:3

0093

147

Class = 93 (DPI Parameter Object)

N30:4

0000

0

Instance = Class Attributes (drive)

N30:5

0000

0

Attribute = 0 (Parameter Value)

N30:6

008D

141

Parameter Number Written To = 141 [Accel Time 2]

N30:7

006F

(2)

(2)

For PowerFlex 700S or PowerFlex 750-Series drives, if some of the parameters being written to are floating point

(REAL) data types, see the ‘Communications’ section in Chapter 1 of the PowerFlex 700S AC Drives Phase II

Control Reference Manual, publication PFLEX-RM003, on how to manipulate REAL data into two 16-bit

registers.

111

Parameter Value Written (LSW) = 11.1 seconds

N30:8

0000

(2)

0

Parameter Value Written (MSW) = 0

N30:9

008F

143

Parameter Number Written To = 143 [Decel Time 2]

N30:10

00DE

(2)

222

Parameter Value Written (LSW) = 22.2 seconds

N30:11

0000

(2)

0

Parameter Value Written (MSW) = 0

N30:12

0069

105

Parameter Number Written To = 105 [Preset Speed 5]

N30:13

014D

(2)

333

Parameter Value Written (LSW) = 33.3 seconds

N30:14

0000

(2)

0

Parameter Value Written (MSW) = 0

N30:15

006A

106

Parameter Number Written To = 106 [Preset Speed 6]

N30:16

01BC

(2)

444

Parameter Value Written (LSW) = 44.4 seconds

N30:17

0000

(2)

0

Parameter Value Written (MSW) = 0

N30:18

006B

107

Parameter Number Written To = 107 [Preset Speed 7]

N30:19

022B

(2)

555

Parameter Value Written (LSW) = 55.5 seconds

N30:20

0000

(2)

0

Parameter Value Written (MSW) = 0