E-4

Master-Slave I/O Configuration

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

M-S Output Parameter
Configurations

Parameter 26 - [M-S Output] has the following five configurable bits.

Figure E.2 Parameter 26 - [M-S Output] Bits and Corresponding I/O

When you enable Cmd/Ref or Datalink in the adapter, you must set the
corresponding bit in Parameter 26 - [M-S Output] if you want the output
data to be sent to the scanner or master device.

Table E.C

and

Table E.D

list possible configurations for Parameter 26 -

[M-S Output] and the possible data size allocation associated with each
value depending on the method of data transfer.

10100

xxxx1

16

16

16

16 and 0

16 and 0

10101

xxxx1

24

24

24

24 and 0

24 and 0

10110

xxxx1

24

24

24

24 and 0

24 and 0

10111

xxxx1

32

32

32

32 and 0

32 and 0

11000

xxxx1

16

16

16

16 and 0

16 and 0

11001

xxxx1

24

24

24

24 and 0

24 and 0

11011

xxxx1

32

32

32

32 and 0

32 and 0

11100

xxxx1

24

24

24

24 and 0

24 and 0

11101

xxxx1

32

32

32

32 and 0

32 and 0

11110

xxxx1

32

32

32

32 and 0

32 and 0

11111

xxxx1

40

40

40

40 and 0

40 and 0

Table E.B Host Products with 32-bit Reference/Feedback and Datalinks (Continued)

M-S Input

M-S Output

Allocation (Number of Bytes)
Data Size sent from the Controller to the Adapter
Poll Only

COS Only

Cyclic Only Poll & COS Poll & Cyclic

Table E.C Host Products with 16-bit Reference/Feedback and Datalinks

M-S Input

M-S Output

Allocation (Number of Bytes)
Data Size sent from the Adapter to the Controller
Poll Only

COS Only

Cyclic Only Poll & COS Poll & Cyclic

xxxxx

00000

0

xxxxx

00010

4

xxxxx

00100

4

xxxxx

00110

8

xxxxx

01000

4

xxxxx

01010

8

xxxxx

01100

8

xxxxx

11100

12

xxxxx

10000

4

xxxxx

10010

8

xxxxx

10100

8

xxxxx

10110

12

xxx0 0000

Datalink D

Datalink C

Datalink B

Datalink A

Cmd/Ref

0 = Peer or other output

1 = Master-Slave output