Commissioning the adapter, Commissioning the adapter -10 – Rockwell Automation 20-COMM-D DeviceNet Adapter Series B FRN 2.xxx User Manual

Page 28

Advertising
background image

2-10

Installing the Adapter

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

3. Verify that drive Parameter 213 - [Speed Ref Source] is reporting that

the source of the Reference to the drive is ‘22’ (DPI Port 5).

This ensures that any Reference commanded from the network can be
monitored by using drive Parameter 002 - [Commanded Speed]. If a
problem occurs, this verification step provides the diagnostic capability
to determine whether the drive/adapter or the network is the cause.

Commissioning the Adapter

To commission the adapter, you must set a unique node address on the
network. See

Setting the Node Address on page 3-3

, and the

Glossary

for

details about node addresses.

Important: New settings for some adapter parameters are recognized only

when power is applied to the adapter or it is reset. After you
change parameter settings, cycle power or reset the adapter.

TIP: For PowerFlex 750-Series drives, use drive Parameter 545 -
[Speed Ref A Sel] to set the drive speed Reference:

a. Set the Port field to ‘Port 0 - PowerFlex 75x’.

b. Set the Parameter field to point to the port in which the

20-COMM-D adapter/20-750-20COMM Communication Carrier
Card are installed (for example, ‘876 - Port 6 Reference’).

The number ‘876’ in the Parameter field of the example is the
parameter in the drive that points to the port.

Advertising