Configuring the I/O

4-21

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

Use RSNetWorx for DeviceNet to Configure and Save the I/O to the

Controller

To establish an I/O configuration that can be used between the controller
and drive over a DeviceNet network, you must first create an I/O image for
the 1771-SDN scanner.

1. Start RSNetWorx for DeviceNet software.

2. In the RSNetWorx for DeviceNet window, select File > New to display

the New File screen.

3. Select ‘DeviceNet Configuration’ as the network configuration type.

4. Click OK.

Drive Parameter No.

Setting

(1)

(1)

Since the PowerFlex 70 EC drive uses 16-bit Datalinks, two contiguous

Datalinks (for example, Data Out A1/A2) are required when assigning a

32-bit parameter such as Parameter 003 - [Output Current]. For drives

with 32-bit Datalinks, only one Datalink is required.

90 - [Speed Ref A Sel]

22 (DPI Port 5)

300 - [Data In A1]

140 (Accel Time 1)

301 - [Data In A2]

142 (Decel Time 1)

302 - [Data In B1]

100 (Jog Speed)

303 - [Data In B2]

155 (Stop Mode A)

304 - [Data In C1]

101 (Preset Speed 1)

305 - [Data In C2]

102 (Preset Speed 2)

306 - [Data In D1]

103 (Preset Speed 3)

307 - [Data In D2]

104 (Preset Speed 4)

310 - [Data Out A1]

140 (Accel Time 1)

311 - [Data Out A2]

142 (Decel Time 1)

312 - [Data Out B1]

100 (Jog Speed)

313 - [Data Out B2]

155 (Stop Mode A)

314 - [Data Out C1]

101 (Preset Speed 1)

315 - [Data Out C2]

102 (Preset Speed 2)

316 - [Data Out D1]

103 (Preset Speed 3)

317 - [Data Out D2]

104 (Preset Speed 4)