Setting the fault configuration parameters, Resetting the adapter, Resetting the adapter -12 – Rockwell Automation 20-COMM-D DeviceNet Adapter Series B FRN 2.xxx User Manual

Page 40

Advertising
background image

3-12

Configuring the Adapter

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

Changes to these parameters take effect immediately. A reset is not
required.

If communication is disrupted and then is re-established, the drive will
automatically take commands from the network again.

Setting the Fault Configuration Parameters

When setting Parameter 10 - [Comm Flt Action] or 11 - [Idle Flt Action]
to ‘Send Flt Cfg’, the values in the following parameters are sent to the drive
after an I/O communication fault and/or idle fault occurs. You must set
these parameters to values required by your application.

Changes to these parameters take effect immediately. A reset is not
required.

Resetting the Adapter

Changes to switch settings and some adapter parameters require that you
reset the adapter before the new settings take effect. You can reset the
adapter by power cycling the drive or by using Parameter 09 - [Reset
Module]
.

Set Parameter 09 - [Reset Module] to ‘1’ (Reset Module).

Parameter

Description

15 - [Flt Cfg Logic]

A 16-bit value sent to the drive for Logic Command.

16 - [Flt Cfg Ref]

A 32-bit value (0…4294967295) sent to the drive as a Reference or Datalink.

Important: If the drive uses a 16-bit Reference or 16-bit Datalinks, the most

significant word of the value must be set to zero (0) or a fault will occur.

17 - [Flt Cfg x1 In]

through

24 - [Flt Cfg x2 In]

Port 5 Device
20-COMM-D
Parameter #: 10

Comm Flt Action

0

Fault

Port 5 Device
20-COMM-D
Parameter #: 11

Idle Flt Action

0

Fault

!

ATTENTION: Risk of injury or equipment damage exists. If the
adapter is transmitting control I/O to the drive, the drive may fault
when you reset the adapter. Determine how your drive will
respond before resetting a connected adapter.

Value

Description

0

Ready (Default)

1

Reset Module

2

Set Defaults

Port 5 Device
20-COMM-D
Parameter #: 09

Reset Module

1

Reset Module