Using the I/O

5-11

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

Regardless of the Datalink combination, Datalink x1 Out will always
contain the LSW and Datalink x2 Out will always contain the MSW. In the
following example, the PowerFlex 70 drive parameter 242 - [Power Up
Marker] contains a value of 88.4541 hours.

Conversion Example:

Parameter 242 - [Power Up Marker]

= 88.4541 hours

MSW = 000D

hex

= 1101

binary

= 2

19

+ 2

18

+ 2

16

= 851968

LSW = 7F3D

hex

= 32573

Engineering Value = 851968 + 32573 = 884541
Parameter 242 Displayed Value = 88.4541 Hrs

Example Ladder Logic

Program Information

The example ladder logic programs in the sections of this chapter are
intended for and operate PowerFlex 7-Class drives.

Functions of the Example Programs

The example programs enable you to do the following:

• Receive Logic Status information from the drive.

• Send a Logic Command to control the drive (for example, start, stop).

• Send a Reference to the drive and receive Feedback from the drive.

• Send/receive Datalink data to/from the drive.

Logic Command/Status Words

These examples use the Logic Command word and Logic Status word for
PowerFlex 70/700 drives. See

Appendix D

to view details. The definition of

the bits in these words may vary if you are using a different DPI drive. See
the documentation for your drive.

Datalink

Word

Parameter

Data (Hex)

A2 Out

MSW

242

000D

B1 Out

LSW

242

7F3D