Configuring the I/O

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

1. Set adapter Parameters 13 - [DPI I/O Cfg], 25 - [M-S Input], and 26 -

[M-S Output] to values that meet your application requirements.

For this example, the adapter I/O parameters are set to these values.

2. Reset the adapter (see

Resetting the Adapter on page 3-12

), or power

cycle the drive.

The drive speed reference and Datalink parameter values, and the
adapter setup parameters for this example are shown below.

Use RSNetWorx for DeviceNet to Configure and Save the I/O to the

Controller

To establish an I/O configuration that can be used between the controller
and drive over a DeviceNet network, you must first create an I/O image for
the 1747-SDN scanner.

1. Start RSNetWorx for DeviceNet software.

2. In the RSNetWorx for DeviceNet window, select File > New to display

the New File screen.

Adapter Parameter No.

Setting

13 - [DPI I/O Cfg]

xxxx xxxx xxx1 1111

25 - [M-S Input]

xxxx xxxx xxx1 1111

26 - [M-S Output]

xxxx xxxx xxx1 1111

Drive Parameter No.

Setting

(1)

(1)

Since the PowerFlex 70 EC drive uses 16-bit Datalinks, two contiguous

Datalinks (for example, Data Out A1/A2) are required when assigning a

32-bit parameter such as Parameter 003 - [Output Current]. For drives

with 32-bit Datalinks, only one Datalink is required.

90 - [Speed Ref A Sel]

22 (DPI Port 5)

300 - [Data In A1]

140 (Accel Time 1)

301 - [Data In A2]

142 (Decel Time 1)

302 - [Data In B1]

100 (Jog Speed)

303 - [Data In B2]

155 (Stop Mode A)

304 - [Data In C1]

101 (Preset Speed 1)

305 - [Data In C2]

102 (Preset Speed 2)

306 - [Data In D1]

103 (Preset Speed 3)

307 - [Data In D2]

104 (Preset Speed 4)

310 - [Data Out A1]

140 (Accel Time 1)

311 - [Data Out A2]

142 (Decel Time 1)

312 - [Data Out B1]

100 (Jog Speed)

313 - [Data Out B2]

155 (Stop Mode A)

314 - [Data Out C1]

101 (Preset Speed 1)

315 - [Data Out C2]

102 (Preset Speed 2)

316 - [Data Out D1]

103 (Preset Speed 3)

317 - [Data Out D2]

104 (Preset Speed 4)