Rockwell Automation 20-COMM-D DeviceNet Adapter Series B FRN 2.xxx User Manual
Page 146
6-18
Using Explicit Messaging
20-COMM-D DeviceNet Adapter User Manual
Publication 20COMM-UM002G-EN-P
ControlLogix Controller Example Scattered Write Request Data
In this message example, we use the data structure in
Figure 6.18
in the
source tag (Scattered_Write_Request) to write new values to these
parameters.
Figure 6.18
shows the parameter values.
Figure 6.18 Example Scattered Write Request Data
ControlLogix Controller Example Scattered Write Response Data
The results of the message appear in the destination tag named
Scattered_Write_Response (
Figure 6.19
). Values of ‘0’ indicate no errors
occurred.
Figure 6.19 Example Scattered Write Response Data
PowerFlex 7-Class Drive Parameter
Write Value
141 - [Accel Time 2]
11.1 Sec.
143 - [Decel Time 2]
22.2 Sec.
105 - [Preset Speed 5]
33.3 Hz.
106 - [Preset Speed 6]
44.4 Hz.
107 - [Preset Speed 7]
55.5 Hz.