Rockwell Automation 20-COMM-D DeviceNet Adapter Series B FRN 2.xxx User Manual

Page 70

Advertising
background image

4-28

Configuring the I/O

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

f. For the Input Size and Output Size boxes, use the pull-down menus

to choose the number of bytes that are required for your I/O.

The size will depend on the drive’s Reference/Feedback and the
number of Datalinks used in your I/O (enabled with adapter
Parameter 13 - [DPI I/O Cfg]), and the selected data exchange
method. (A 16-bit word is two bytes, and a 32-bit word is four
bytes.) For this example, an Input Size of ‘20’ and an Output Size
of ‘20’ are used.

Important:Make sure that the bits for Parameters 25 - [M-S

Input] and 26 - [M-S Output] are set to match
Parameter 13 - [DPI I/O Cfg]. See

Setting a

Master-Slave Hierarchy (Scanner-to-Drive
Communication) on page 3-5

for details.

Table 4.E

,

Table 4.F

, or

Table 4.G

list the number of bytes required

for the Input Size and Output Size boxes for specific I/O
configurations—and only the Polled data exchange method. For
Input Sizes and Output Sizes for other data exchange methods and
specific I/O configurations, see the tables in

Appendix E

.

Table 4.E Drives with 16-bit Reference/Feedback and 16-bit Datalinks

These products include the following:

Table 4.F Drives with 16-bit Reference/Feedback and 32-bit Datalinks

These products include the following:

• PowerFlex 70 drives with standard or enhanced control

• SMC Flex smart motor controllers

• PowerFlex 700 drives with standard control

• SMC-50 smart motor controllers

• PowerFlex 700H drives

Logic

Command/

Status

Ref/Fdbk

(16-bit)

Datalinks (16-bit) User Configured Settings

A

B

C

D

Size in Bytes

Par. 13 -

[DPI I/O Cfg]

Par. 25 -

[M-S Input]

Par. 26 -

[M-S Output]

Input Output

4

4

…0 0001

…0 0001

…0 0001

8

8

…0 0011

…0 0011

…0 0011

12

12

…0 0111

…0 0111

…0 0111

16

16

…0 1111

…0 1111

…0 1111

20

20

…1 1111

…1 1111

…1 1111

• PowerFlex 700 drives with vector control

• PowerFlex Digital DC drives

• PowerFlex 700L drives with 700 control

Logic

Command/

Status

Ref/Fdbk

(16-bit)

Datalinks (32-bit) User Configured Settings

A

B

C

D

Size in Bytes

Par. 13 -

[DPI I/O Cfg]

Par. 25 -

[M-S Input]

Par. 26 -

[M-S Output]

Input Output

4

4

…0 0001

…0 0001

…0 0001

12

12

…0 0011

…0 0011

…0 0011

20

20

…0 0111

…0 0111

…0 0111

28

28

…0 1111

…0 1111

…0 1111

36

36

…1 1111

…1 1111

…1 1111