Rockwell Automation 20-COMM-D DeviceNet Adapter Series B FRN 2.xxx User Manual

Page 48

Advertising
background image

4-6

Configuring the I/O

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

The following screen shows our example navigating to devices that are
on a DeviceNet network. Depending on the communication link you are
using, the navigation path may be different.

7. After selecting a valid path to the DeviceNet network (for this example,

A, DeviceNet), click OK.

If a message box appears about uploading or downloading information,
click OK.

As the selected DeviceNet path is browsed, RSNetWorx for DeviceNet
creates a graph view window that shows a graphical representation of
the devices on the network.

If the icon for the drive (for this example, PowerFlex 70 EC) on the
network appears as Unrecognized Device, either use RSNetWorx for
DeviceNet software to create the appropriate drive EDS file or
download the EDS file from the Rockwell Automation website.

Important: If you will be using the optional DeviceNet Tag Generator

to create descriptive controller tags (

page 4-16

), you must

download and use the EDS file from the website.

Advertising