Installing the Adapter

2-9

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

Table 2.A Drive and Adapter Start-Up Status Indications

For more details on status indicator operation, see

page 7-2

and

page 7-3

.

Configuring and Verifying Key Drive Parameters

The PowerFlex 7-Class drive can be separately configured for the control
and Reference functions in various combinations. For example, you could
set the drive to have its control come from a peripheral or terminal block
with the Reference coming from the network. Or you could set the drive to
have its control come from the network with the Reference coming from
another peripheral or terminal block. Or you could set the drive to have both
its control and Reference come from the network.

The following steps in this section assume that the drive will receive the
Logic Command and Reference from the network.

1. Use drive Parameter 090 - [Speed Ref A Sel] to set the drive speed

Reference to ‘22’ (DPI Port 5).

2. If hard-wired discrete digital inputs are not used to control the drive,

verify that unused digital input drive Parameters 361 - [Dig In1 Sel] and
366 - [Dig In2 Sel] are set to ‘0’ (Not Used).

Item Name

Color

State

Description

Drive STS Indicator

STS

(Status)

Green

Flashing

Drive ready but not running, and no faults are present.

Steady

Drive running, no faults are present.

Yellow

Flashing,

drive stopped

An inhibit condition exists – the drive cannot be

started. Check drive Parameter 214 - [Start Inhibits].

Flashing,

drive running

An intermittent type 1 alarm condition is occurring.

Check drive Parameter 211 - [Drive Alarm 1].

Steady,

drive running

A continuous type 1 alarm condition exists. Check

drive Parameter 211 - [Drive Alarm 1].

Red

Flashing

A fault has occurred.

Steady

A non-resettable fault has occurred.

Adapter Status Indicators

PORT

Green

Flashing

Normal operation. The adapter is establishing an I/O

connection to the drive. It will turn steady green or red.

Steady

Normal operation. The adapter is properly connected

and communicating with the drive.

MOD

Green

Flashing

Normal operation. The adapter is operating but is not

transferring I/O data to a controller.

Steady

Normal operation. The adapter is operating and

transferring I/O data to a controller.

NET A

Green

Flashing

Normal operation. The adapter is properly connected

but does not have an I/O connection.

Steady

Normal operation. The adapter is properly connected

and communicating on the network.

NET B

Not used by DeviceNet adapter.