Plc-5 controller examples, Plc-5 controller examples -19 – Rockwell Automation 20-COMM-D DeviceNet Adapter Series B FRN 2.xxx User Manual

Page 147

Advertising
background image

Using Explicit Messaging

6-19

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

PLC-5 Controller Examples

To perform explicit messaging on a DeviceNet network with a PLC-5
controller, a combination of a block transfer read and a block transfer write
must be used (

Figure 6.20

).

Figure 6.20 PLC-5 Example Ladder Logic Program for All Explicit Messaging

PLC-5 Controller Example to Read a Single Parameter

A read message is used to read a single parameter. This read message
example reads the value of parameter 003 - [Output Current] in a PowerFlex
7-Class drive.

Table 6.H Example Single Read Request Data

Address

Value

Description

Hex.

(1)

(1)

In RSLogix 5 software, leading zeros are not displayed in data file addresses. For example, ‘0008’ in address

N30:1 is shown as ‘8’.

Dec.

N30:0

0101

257

TXID = 01, Command = 01 (execute)

N30:1

0008

8

Port = 00, Size = 08 bytes

N30:2

0E01

3585

Service = 0E (Get_Attribute_Single), Address = 01 (Node)

N30:3

0093

147

Class = 93 (DPI Parameter Object)

N30:4

0003

3

Instance = Parameter 3

N30:5

0009

9

Attribute = 9 (Parameter Value)

Advertising