Rockwell Automation 20-COMM-D DeviceNet Adapter Series B FRN 2.xxx User Manual

Page 168

Advertising
background image

6-40

Using Explicit Messaging

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

Table 6.S Example Single Write COP Response Data

Figure 6.45 Example Single Write COP Response Data File

SLC 500 Controller Example COP Message to Read Multiple Parameters

A scattered read message is used to read the values of multiple parameters.
Up to 8 parameters can be read. This read message example reads the values
of these five parameters in a PowerFlex 7-Class drive:

• Parameter 001 - [Output Freq]

• Parameter 003 - [Output Current]

• Parameter 006 - [Output Voltage]

• Parameter 012 - [DC Bus Voltage]

• Parameter 017 - [Analog In2 Value]

Address

Value

Description

Hex.

(1)

(1)

In RSLogix 5 software, leading zeros are not displayed in data file addresses. For example, ‘0000’ in address

N30:71 is shown as ‘0’.

Dec.

N30:70

0101

257

TXID = 01, Status = 01 (successful)

N30:71

0000

0

Port = 00, Size = 00 bytes

N30:72

9001

-28671

Service = 90 (successful), Address = 01 (Node)