Using Explicit Messaging

6-21

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

PLC-5 Controller Example to Write a Single Parameter

A write message is used to write to a single parameter. This write message
example writes a value of 10.0 seconds to parameter 140 - [Accel Time 1] in
a PowerFlex 7-Class drive.

Table 6.J Example Single Write Request Data

Figure 6.23 Example Single Write Request Data File

Address

Value

Description

Hex.

(1)

(1)

In RSLogix 5 software, leading zeros are not displayed in data file addresses. For example, ‘0008’ in address

N30:1 is shown as ‘8’.

Dec.

N30:0

0101

257

TXID = 01, Command = 01 (execute)

N30:1

0008

8

Port = 00, Size = 08 bytes

N30:2

1001

4097

Service = 10 (Set_Attribute_Single), Address = 01 (Node)

N30:3

0093

147

Class = 93 (DPI Parameter Object)

N30:4

008C

140

Instance = Parameter 140

N30:5

0009

(2)

(2)

Setting the data file address value to ‘9’ will write the parameter value to the drive’s Nonvolatile Storage

(EEPROM) memory, which retains the parameter value even after the drive is power cycled.

Important: When

set to ‘9’, the EEPROM may quickly exceed its life cycle and cause the drive to malfunction. Setting the data file

address value to ‘A’ (Hex.) will write the parameter value to temporary memory, which deletes the parameter

value after the drive is power cycled. When frequent write messages are required, we recommend using the ‘A’

setting.

9

Attribute = 9 (Parameter Value)

N30:6

0064

(3)

(3)

In this example, Accel Time 1 is a 16-bit integer parameter. The most significant word (MSW) is not used. For

PowerFlex 700S or PowerFlex 750-Series drives, Accel Time 1 is a floating point number. To manipulate REAL

data into two 16-bit registers, see the ‘Communications’ section in Chapter 1 of the PowerFlex 700S AC Drives

Phase II Control Reference Manual, publication PFLEX-RM003.

100

Parameter Value Written (LSW) = 10.0 seconds

N30:7

0000

(3)

0

Parameter Value Written (MSW) = 0