B-4

Adapter Parameters

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

15

[Flt Cfg Logic]
Sets the Logic Command data that is sent to the

drive if any of the following is true:
Parameter 10 - [Comm Flt Action] is set to ‘4’

(Send Flt Cfg) and I/O communication is

disrupted.

Parameter 11 - [Idle Flt Action] is set to ‘4’

(Send Flt Cfg) and the controller is idle.

Parameter 34 - [Peer Flt Action] is set to ‘4’

(Send Flt Cfg) and peer I/O communication is

disrupted.

The bit definitions will depend on the product to

which the adapter is connected. See

Appendix D

or the documentation for the drive being used.

Default:

0000 0000 0000 0000

Minimum:

0000 0000 0000 0000

Maximum:

1111 1111 1111 1111

Type:

Read/Write

Reset Required: No

16

[Flt Cfg Ref]
Sets the Reference data that is sent to the drive if

any of the following is true:
Parameter 10 - [Comm Flt Action] is set to ‘4’

(Send Flt Cfg) and I/O communication is

disrupted.

Parameter 11 - [Idle Flt Action] is set to ‘4’

(Send Flt Cfg) and the controller is idle.

Parameter 34- [Peer Flt Action] is set to ‘4’

(Send Flt Cfg) and peer I/O communication is

disrupted.

Default:

0

Minimum:

0

Maximum:

4294967295

Type:

Read/Write

Reset Required: No
Important: If the drive uses a 16-bit

Reference, the most significant word of

this value must be set to zero (0) or a

fault will occur.

17

18

19

20

21

22

23

24

[Flt Cfg A1 In]

[Flt Cfg A2 In]

[Flt Cfg B1 In]

[Flt Cfg B2 In]

[Flt Cfg C1 In]

[Flt Cfg C2 In]

[Flt Cfg D1 In]

[Flt Cfg D2 In]
Sets the data that is sent to the Datalink in the

drive if any of the following is true:
Parameter 10 - [Comm Flt Action] is set to ‘4’

(Send Flt Cfg) and I/O communication is

disrupted.

Parameter 11 - [Idle Flt Action] is set to ‘4’

(Send Flt Cfg) and the controller is idle.

Parameter 34 - [Peer Flt Action] is set to ‘4’

(Send Flt Cfg) and peer I/O communication is

disrupted.

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Minimum:

0

Maximum:

4294967295

Type:

Read/Write

Reset Required: No
Important: If the drive uses 16-bit

Datalinks, the most significant word of

this value must be set to zero (0) or a

fault will occur.

25

[M-S Input]
Sets the Master-Slave input data. This data is

produced by the scanner and consumed by the

adapter.

Default:

xxx0 0001

Bit Values:

0 = I/O Disabled

1 = I/O Enabled

Type:

Read/Write

Reset Required: Yes

Parameter
No. Name and Description

Details

Bit

Definition

Not

Used

Not

Used

Not

Used

Datalink

D

Input

Datalink

C

Input

Datalink

B

Input

Datalink

A

Input

Cmd/

Ref

Default

x

x

x

0

0

0

0

1

Bit

7

6

5

4

3

2

1

0