Configuring the I/O

4-11

20-COMM-D DeviceNet Adapter User Manual

Publication 20COMM-UM002G-EN-P

d. Click Edit I/O Parameters… to display the Edit I/O Parameters

screen for the PowerFlex 70 EC drive used in this example.

e. Select the type of data exchange (Polled, Change of State, and/or

Cyclic).

For this example, we selected (and recommend) Polled.

f. For the Input Size and Output Size boxes, use the pull-down menus

to choose the number of bytes that are required for your I/O.

The size will depend on the drive’s Reference/Feedback and the
number of Datalinks used in your I/O (enabled with adapter
Parameter 13 - [DPI I/O Cfg]), and the selected data exchange
method. (A 16-bit word is two bytes, and a 32-bit word is four
bytes.) For this example, an Input Size of ‘20’ and an Output Size
of ‘20’ are used.

Important:Make sure that the bits for Parameters 25 - [M-S

Input] and 26 - [M-S Output] are set to match
Parameter 13 - [DPI I/O Cfg]. See

Setting a

Master-Slave Hierarchy (Scanner-to-Drive
Communication) on page 3-5

for details.

Table 4.A

,

Table 4.B

, or

Table 4.C

list the number of bytes required

for the Input Size and Output Size boxes for specific I/O
configurations—and only the Polled data exchange method. For
Input Sizes and Output Sizes for other data exchange methods and
specific I/O configurations, see the tables in

Appendix E

.