Rockwell Automation 20-COMM-D DeviceNet Adapter Series B FRN 2.xxx User Manual
Page 69

Configuring the I/O
4-27
20-COMM-D DeviceNet Adapter User Manual
Publication 20COMM-UM002G-EN-P
c. Click ‘>’ to move the PowerFlex 70 EC drive to the Scanlist box.
d. Click Edit I/O Parameters… to display the Edit I/O Parameters
screen for the PowerFlex 70 EC drive used in this example.
e. Select the type of data exchange (Polled, Change of State, and/or
Cyclic).
For this example, we selected (and recommend) Polled.
Box
Setting
Node Active
Activates/deactivates the scanlist in the 1771-SDN scanner for
the selected device. For this example, keep the box checked.
Device Type
These Electronic Key category check boxes select how specific
the device in the scanlist must be for the 1771-SDN scanner to
match its compatibility for I/O operation. The more boxes that
are checked, the more specific the device must be to operate.
For this example, keep the default boxes (Device Type, Vendor,
and Product Code) checked.
Vendor
Product Code
Major Revision (only
1771-SDN Series C
version 6.xxx or later)